Amana Furnace Part

QUESTION:

When lubricating furnace motor (Emerson F55HX CBR-1216 RPM 1075/3SPD) The oil (Special blend for motors >1/4HP) leaks out of bearings.
1 IS it normal or should I get a spare motor soon?
(The motors runs smooth and quiet so the bearings are still OK but maybe seal is gone.)
2 IS replacement of bearings cost effective?
3 I would like to change the control and use the other leg of the SPDT contact that controls the fan to energize a low speed winding. Is it OK to do it. I realize that the fan will be ON all the time Medium speed when heating/cooling and Low speed afterwards.
4 Eventually I would like to incorporate a cycler in the low speed control. Do you know of any "of the shelf" cycler suitable for that. (Home Depot stuff)
5. Ideally the cycler would be outside temperature modified.
(the cooler it gets the longer the ON cycle) Am I pushing now or is there something on the market that would do the job?

ANSWER:

Running the fan constantly during cooling days is recommended practice for reducing air conditioning costs -
1. maintaining an airflow of 15 fpm across the occupants (ASHRAE standard for AC) creates natural occupant cooling and minimizes stratification, and thus will allow the AC to be set several degrees higher temperature with the same comfort level than can a stop-start system. In northern climes, where the dual-purpose registers are installed near the floor, start-stop will definitely cause stratification and a layer of cold air pooling at the floor.
2. In insulated structures, the cooling air being run across the walls reduces the wall and furnishings mass temperature in off-peak times and has a thrombic wall effect (the AC can "store up" heat removal and tap into it to reduce total need on the unit during the high load demand portions of the day)
3. Fan bearing wear is significantly less when constant-run than with start-stop. The wear on a sleeve bearing comes primarily during start and stop, when the pressure on the bearing from the shaft is unevenly distributed, and when force is also higher due to the higher start-up torque of the motor and stopping inertia of the squirrel cage and air mass, and when the shaft-bearing oil film that is in place during running is no longer in place, since the shaft is stopped. Wear being a fourth power effect of force, the net wear is significantly more during stop-start A constant-run unlubricated bronze bushing can be run indefinitely without liquid lubrication if properly sized. Lubricant is rarely lost in constant run applications (being kept in by capillary action) but does need to be replenished in start-stop (it seeps out of the bearing-shaft interface during the off time)
(If improper lubricant is used or the bearing is mis-sized, the oil will oxidize and gum and then heat the bearing and squeek, and new oil will be needed to clean off the old oil. Sintered bearings, commonly used in furnace fans, have a low-oxidizing-oil reservoir in the sinter, and rarely if ever need new oil.)
(Some studies hold that the current inrush and additional current used to start the airmass in start-stop is approximately equal to the constant-run current used in most residential heating)
4. In dwellings with basements, constant-run allows a constant slight positive pressure to be kept in the basement, stopping moisture migration into the basement - (stops damp basements), and the moving air scavenges any moisture fromt eh baement (note- basement intake registers, if installed, need to be closed to get
As to water being re-introduced -
1. the uncharged coils should reach ambient temperature in under a minute if the fan is moving air and the compressor stopped. Water collects on the coils due to condensation of water vapor (from within the dwelling) because the coils are a lower temperature than the ambient air temperature, due to the liquid charge evaporating at the cooling coil exchanger
- since the compressor is off and the coil has taken on the ambient air heat to raise its own temperature to ambient, it will not collect more water from the air within a minute after the compressor shuts off.
2. if running the fan causes the water in the pan to go back into the house, the drain is plugged or improperly installed - any water in the pan should go out the drain line first from gravity and secondly from a slightly positive pressure in the ambient-temperature-side of the cooling-coil heat exchanger in the plenum corners.
>In the heating system it makes a little more sense to run the fan all the
>time but not much. Those 3 speed fans aren't particularly efficient at any
>speed. Running it all the time can easily cost you $100 or MORE a year.
Constant running of a forced-air fan in the colder months in the north is much more efficient than stop-start - partly from fan wear and running costs (see above) and also from (see ASHRAE)
1. stratification - lower ambient temperatures can be used with the same comfort level constant-run since the temperature gradient can be below the 1 degree f per foot that causes discomfort in most occupants
2. Local surfaces - "wall-washing" registers maintain heat on the outer walls and allow the thermostat to be set as much as 5 degrees F lower with the same comfort level as start-stop.
3. humidity levels can be kept up in comfort ranges since more air moves across the transfer surface and since the air moves across sills and glass, evaporating/subliming any moisture/ice that would otherwise collect at the same humidity levels in a start-stop system.
with proper filters, the air in the dwelling is cleaner with constant-run, adding life to draperies and minimizing swelling and shrinking of wood furniture. The wood and the air quality are
As all installatioons are slightly different, one should check the use of electricty and fuel in your particular situation, billing period on start-stop, billing period on constant, start-stop, and then copsntant again - and normalize the use against the number of degree days (cooling degree days) needed for the period, as indicated on the fuel bill (or available from the power comany), e.g, if you use 500 kw and 1000 ccf gas running constant in a month needing 1000 degree days, thermostat set for comfort under constant conditions, and the combined fuel-power costs were $100 that period, then divide the combined cost by the degree days. The next billing period, the start-stop one, do the same calculation and compare. Then if you have a higher run than start-stop cost (poosible in the south in winter, or in the north in summer) guesstimate the worth of the fan wear and basement dampness and see if you should run constant all year, part year, or at all.
for more detailed info, see the ASHRAE manuals on HVAC
--- personally, my forced air furnace fan has run constantly since 1978, with stops only to change the Aprilaire super-filters once a year and for "burner" maintenance (igniter). The registers have wall washer type registers My basement hasn't been damp since it went constant, my fuel bill is quite low (lowest around here even though my house is bigger than most near here, although some of that savings is attributable to the "old" Hi Eff Amana furnace) and short sleeves in winter inside is not unusual. I have many large e-glass windows, and outside of the 24" insulation in the attic, it has the original 1960 insulation. My AC is a 2 1/2 ton, 2 roof power vents, and they have done quite well at keeping us at 78 F on even those days long 95 F 95% humidity days this summer with incessant energy save switch-outs- (in the great room, I do change out the winter wall washer registers for hi-throw cooling registers for summer use.)


Submit your comment or answer




Privacy Policy