boiler layout ?

QUESTION:

I have a problem with a system that serves vav boxes. my problem is that the system is running constantly and I dont know where my water is disappearing to but I nee to fill it often. My fead supply is on the discharge side of the pump so as long as the pump is running I am above the standard 12psi pressure that the regulator supplies at. My vav hat water supply is controlled by a two way valve that lets the water bypass the exchanger and back into the return piping. My problem is or I think my problem is , while my water leaks out in time a few weeks or so I am not getting any new water added due to supply pres and due to the loss of water my suction presser drops into a negative pres causing air to be sucked into into the return through the air bleeds. I am not sure if the water feed should be on the return or the supply side of the pump,and weather the air bleeds should be on the return or supply side. I think I need to program it to shut down at least an hour a day to help with the feed. DOES ANYONE HAVE A BOILER DIAGRAM ( LAYOUT) THEY CAN SEND ME?

ANSWER:

You have nailed the issue - water is leaving what should be ( from your description ) a closed system. Not good.
There is no magic answer here - you need to find the point of exit, and the cause of it.
Likely source would be T&P valves periodically discharging. Put a piece of paper towel under the discharge of all T&P valves on the system ( don't block them or their drains ! ). Check them periodically. If they show signs of being or having been wet, you have your answer ( or part of it ).
Less likely ( I hope ! ) would be breaks in the piping, or drain valves open / partially open.