Gas Floor Furnace

QUESTION:

I have Virginia house built in 1936 that has gas floor furnace heat. We have lived there for 10 years. Over the past 4 years, the furnace has been getting harder and harder to get to operate in the fall. The control unit under the house in line with the furnace was replaced several years before we moved in 10 years ago.
1996: Crawl under house and light pilot. Come in house and turn up thermostat, but furnace doesn't fire up. Thinking maybe there is some sort of oxidation inside the mercury vial, I short the terminal on the outside of the mercury vial and the furnace kicks on. Let the furnace run for a few minutes, and the whole system worked good the rest of the winter.
1997: Pretty much the same thing as in 1996.
1998: Pretty much the same thing as in 1996.
1999: After doing the same thing as previous years, still couldn't get furnace to ignite. Replaced the thermostat on the wall with a new one. Still no luck. Went under the house and shorted across the thermostat lugs on the control unit with a wire, and the furnace ignited. Thinking that the terminals or the thermostat wires were oxidized, I undid the thermostat wires and scraped them along with the lug faces and screwed it all back together. System worked well from there (might have had to short across thermostat lugs one more time before I got it running...can't remember exactly).
2000: This year I had to repeat everything that I did in 1999, but there is nothing I can do to get the system to work with the thermostat on the wall. The only way I can get the furnace to fire up is to short across the thermostat wire lug connections on the control unit under the house. If the thermostat is on up in the house, then when I short across the lugs under the house, then it will stay lit when I remove the short. However, once I shut the furnace off via the thermostat in the house, then I cannot get it to re-ignite via the thermostat.
Where could the problem be. Any suggestions? I would love to be able to fix this myself and save on a big repair bill. I have multimeter, so if I need to check voltages or anything I can do that, but just don't know what to look for. By the way the there are three lugs on the control unit. The thermostat wires go to the outer two lugs and the thermopile wires go to the center lug and an outer lug.

ANSWER:

Thermopile means the gas valve is actually powered by the tiny voltage generated from the flame on the thermoplie unit. IIRC, it is about 350mv but there may have been several standards. More than likely, the thermoplie is weak or the pilot flame is not striking it in such a way to maximize the output voltage.


Submit your comment or answer




Privacy Policy