Goodman Gas Furnace

QUESTION:

My 7 year old outdoor Goodman Gas furnace/Ac died 2 weeks ago. First the igniter died and I had that replaced. A week later I started getting a "blowback" from the gas where 1 of the 3 fires wouldn't fully be blown into the heat exchange. The blowback licks off a safety switch that shuts off the unit. My contractor has tried on and off for 2 weeks to fix the problem. He called Goodman and their suggestion was to replace the heat exchanger. Did that yesterday. Still no luck.
Fans running, other appliances OK, pressure he says is OK, swapped the jets around and the ok one won't work on the bad one. I don't know much about HVAC but am starting to learn.

ANSWER:

Sounds like you need the new burner replacement Kit furnished free by Goodman for when the burner will not burn correctly. The Goodman Support team did not know of the burner problem , so just tell your Janitrol / goodman warehouse man to order a burner replacement Kit Part
# 40227-01S . The goodman warehouse man will have in his computor a Burner replacement kit # 40227-01S which is free and is for replacement of defective burn sets install on most all Goodman furnaces back until the did not have vent fans. This is for all GMP models. This is not a problem or a recall yet for no one has filed a suite yet.